Modbus Protocol

Modbus is a messaging protocol that defines the packet sructure for transferring data between devices in a master/slave architecure. The protocol is independent of the transmission medium and is usually transmissed over TCP (MODBUS TCP) or over serial communication (MODBUS RTU). Modbus is intended to be a request/reply protocol and delivers services specified by function codes. The function code in the request tells the addressed slave what kind of action to perform. The function codes most commonly supported by devices are listed below.

Function Name Function Code
Read Coils 0x01
Read Discrete Inputs 0x02
Read Holding Registers 0x03
Read Input Registers 0x04
Write Single Coil 0x05
Write Single Register 0x06
Write Multiple Coils 0x0F
Write Multiple Registers 0x10

For more information on the MODBUS RTU see the following PDF File. Information on the MODBUS TCP can be found here.

Pycom Modbus Library

Python libraries and sample code that support Modbus TCP and Modbus RTU are available at the following GitHub Repository. To use this library, connect to the target Pycom device via ftp and upload the uModbus folder to /flash. A description of the supported function codes is found below.

Read Coils

This function code requests the status (ON/OFF) of discrete coils in a remote device. The slave device address, the address of the first coil and the number of coils must be specified in the request. The address of the first coil is 0 and a maximum of 2000 contiguous coils can be read. Python sample code is shown below.

slave_addr=0x0A
starting_address=0x00
coil_quantity=100

coil_status = modbus_obj.read_coils(slave_addr, starting_address, coil_quantity)
print('Coil status: ' + ' '.join('{:d}'.format(x) for x in coil_status))

Read Discrete Inputs

This command is used to read the status (ON/OFF) of discrete inputs in a remote device. The slave address, the address of the first input, and the quantity of inputs to read must be specified. The address of the first input is 0 and a maximum of 2000 contigous inputs can be read. Python sample code is shown below.

slave_addr=0x0A
starting_address=0x0
input_quantity=100

input_status = modbus_obj.read_discrete_inputs(slave_addr, starting_address, input_quantity)
print('Input status: ' + ' '.join('{:d}'.format(x) for x in input_status))

Read Holding Registers

This function code is used to read the contents of analogue output holding registers. The slave address, the starting register address, the number of registers to read and the signess of the data must be specified. Register addresses start at 0 and a maximum of 125 contigous registers can be read.

slave_addr=0x0A
starting_address=0x00
register_quantity=100
signed=True

register_value = modbus_obj.read_holding_registers(slave_addr, starting_address, register_quantity, signed)
print('Holding register value: ' + ' '.join('{:d}'.format(x) for x in register_value))

Read Input Registers

This command is used to read up to 125 contigous input registers in a remote device. The slave address, the starting register address, the number of input registers and the signess of the data must be specified. The address of the first input registers is 0.

slave_addr=0x0A
starting_address=0x00
register_quantity=100
signed=True

register_value = modbus_obj.read_input_registers(slave_addr, starting_address, register_quantity, signed)
print('Input register value: ' + ' '.join('{:d}'.format(x) for x in register_value))

Write Single Coil

This function code is used to write the state of a dicrete coil in a remote device. A value of 0xFF00 means the coil should be set to ON, while a value of 0x0000 means the coil should be set to OFF. Python sample code to set the coil at address 0x00, to an ON state is shown below.

slave_addr=0x0A
output_address=0x00
output_value=0xFF00

return_flag = modbus_obj.write_single_coil(slave_addr, output_address, output_value)
output_flag = 'Success' if return_flag else 'Failure'
print('Writing single coil status: ' + output_flag)

Write Single Register

This command is used to write the contents of an analog output holding register in a remote device. The slave address, the register address, the register value and the signess of the data must be specified. As for all the other commands, the register addresses start from 0.

slave_addr=0x0A
register_address=0x01
register_value=-32768
signed=True

return_flag = modbus_obj.write_single_register(slave_addr, register_address, register_value, signed)
output_flag = 'Success' if return_flag else 'Failure'
print('Writing single coil status: ' + output_flag)

Write Multiple Coils

This function code is used to set a contigous sequence of coils, in a remote device, to either ON or OFF. The slave address, the starting address of the coils and an array with the coil states must be specified.

slave_addr=0x0A
starting_address=0x00
output_values=[1,1,1,0,0,1,1,1,0,0,1,1,1]

return_flag = modbus_obj.write_multiple_coils(slave_addr, starting_address, output_values)
output_flag = 'Success' if return_flag else 'Failure'
print('Writing multiple coil status: ' + output_flag)

Write Multiple Registers

This command is used to write the contents of a contigous sequence of analogue registers in a remote device. The slave address, the starting register address, the register values and the signess of the data must be specified. The address of the first register is 0 and a maximum of 125 register values can be written. Python sample code is shown below.

slave_addr=0x0A
register_address=0x01
register_values=[2, -4, 6, -256, 1024]
signed=True

return_flag = modbus_obj.write_multiple_registers(slave_addr, register_address, register_values, signed)
output_flag = 'Success' if return_flag else 'Failure'
print('Writing multiple register status: ' + output_flag)